MEASURING RANGES ----------- RCD test Test currents (In): 10 mA / 30 mA / 100 mA / 300 mA / 500 mA / 1000 mA Mains voltage: 100 ~ 440 V ±15%; 45 ~ 65 Hz Trip time ranges: • for 1 In: 0 ~ 2000 ms ±(5%+5) • for 1 In: 0 ~ 500 ms ±(5%+5) • for 2 In: 0 ~ 200 ms ±(5%+5) • for 5 In: 0 ~ 40 ms ±(5%+5) Ramp current measurement Current trip accuracy: 10% Fault loop impedance: Mains voltage (L-E): 220 V ±10%; 45 ~ 65 Hz Test current/time: 20 A/20 ms Measuring ranges: • 0.05 Ohm ~ 1.99 Ohm ±(5%+5) • 2 Ohm ~ 19.9 Ohm ±(5%+5) • 20 Ohm ~ 2000 Ohm ±(5%+5) Safe current measuring range: 0 ~ 26 kA OTHER MEASURING RANGES ----------- Low resistances: 0.01 Ohm ~ 200 Ohm ±(2%+5) AC voltage: 0 ~ 440 V ±(2%+3) DC voltage: 0 ~ 440 V ±(2%+3) Frequency: 20 Hz – 100 Hz (for comparison purposes only) ADDITIONAL FUNCTIONS ----------- Manual/automatic range setting Phase sequence test Low battery indicator High voltage warning Backlit LCD screen Buzzer Secondary display Maximum reading value: 9999 Zero function GENERAL CHARACTERISTICS ----------- Power supply: 8 batteries of 1.5 V (LR6) Dimensions: 161 x 117 x 68 mm Weight: 725 g Included: batteries, test leads, special test lead, test probes, crocodile clips, test probe, case
No imported reviews for this product.