Stationary battery AGM VRLA 12V 7AH MW

Stationary battery AGM VRLA 12V 7AH MW

The 12V7MW battery (usually designated MW 7-12 / MW 7-12L) is a sealed VRLA/AGM battery from MW Power, with a nominal voltage of 12 V and a capacity of 7 Ah (C20), from the standard MW series, intended especially for UPS units, alarm systems, emergency lighting and moderate cyclic applications.

-20% Black Friday
211.68 RON 169.34 RONVAT included
Lowest price in the last 30 days: 211.68 RON
Site stock100
In stock · Delivery is calculated at checkout.
Estimated shipping cost Easybox (Sameday) 9.99 RON Romania, to your address 29.99 RON Hungary, Bulgaria or Greece 49.99 RON
Shipping is calculated transparently before order submission Returns follow the store policy available in the legal pages Payment by card, bank transfer or cash on delivery when available

The 12V7MW battery (usually denoted MW 7-12 / MW 7-12L) is a sealed VRLA/AGM battery from MW Power, with a nominal voltage of 12 V and a capacity of 7 Ah (C20), from the standard MW series, intended in particular for UPS units, alarm systems, emergency lighting and moderate cyclic applications.

Main technical characteristics

Technology: VRLA (Valve Regulated Lead Acid), AGM – sealed, maintenance-free, can be mounted in various positions.
Nominal voltage: 12 V.
Nominal capacity (C20, 25 °C, 10.5 V cut-off):

  • 7.0 Ah at 20 h discharge

~ 6.5 Ah at 10 h
~ 5.6 Ah at 5 h (typical values for the 7 Ah AGM class)

Cycle life: up to ~500 cycles at ~50% depth of discharge.
Typical uses: UPS units, alarm systems and DSO, emergency lighting, automation systems, portable devices, small off-grid photovoltaic systems.

Body dimensions: 151 × 65 × 94 mm (L × W × H).
Total height (with terminals): ~100–102 mm.

Terminals

Faston 187 (T1 / F1) for MW 7-12
Faston 250 (T2 / F2, 6.35 mm) for MW 7-12L

Charging and performance parameters

Standby/float charging: 13.4–13.8 V at 25 °C.
Cyclic charging: 14.4–15.0 V.
Maximum recommended charging current: 2.1 A (maximum), recommended ~0.7–1.0 A in many UPS applications.
Maximum discharge current: up to ~105 A for 5 seconds (peak, not continuous) – typical value for the MW 7 Ah series.
Internal resistance: ~23–25 mOhm (charged battery) – typical value for 7 Ah AGM.

Self-discharge (at 25 °C)

  • after 3 months: ~91% capacity remaining
  • after 6 months: ~82%
  • after 12 months: ~64%