Stationary battery AGM VRLA 12V 17AH MB

Stationary battery AGM VRLA 12V 17AH MB

The 12V17MB battery (usually designated MB 17-12) is a sealed VRLA/AGM battery from megaBAT, with a nominal voltage of 12 V and a capacity of 17 Ah (C20), intended especially for UPS units, alarm systems, emergency lighting, telecommunications and moderate cyclic applications (e.g.

-20% Black Friday
379.55 RON 303.64 RONVAT included
Lowest price in the last 30 days: 379.55 RON
Site stock100
In stock · Delivery is calculated at checkout.
Estimated shipping cost Easybox (Sameday) 9.99 RON Romania, to your address 29.99 RON Hungary, Bulgaria or Greece 49.99 RON
Shipping is calculated transparently before order submission Returns follow the store policy available in the legal pages Payment by card, bank transfer or cash on delivery when available

The 12V17MB battery (usually denoted MB 17-12) is a sealed VRLA/AGM battery from megaBAT, with a nominal voltage of 12 V and a capacity of 17 Ah (C20), intended in particular for UPS units, alarm systems, emergency lighting, telecommunications and moderate cyclic applications (e.g. off-grid solar systems, light electric vehicles).

Main technical characteristics

Technology: VRLA (Valve Regulated Lead Acid), AGM – sealed, maintenance-free, can be mounted in various positions.
Nominal voltage: 12 V.
Nominal capacity (C20, 25 °C, 10.5 V cut-off):

  • 17.0 Ah at 20 h discharge
  • 15.3 Ah at 10 h
  • 12.75 Ah at 5 h (typical values for the 17 Ah AGM class)

Design service life: 3–5 years in buffer (standby) operation, at 20–25 °C, according to EUROBAT for the MB series.
Cycle life: up to ~500 cycles at ~50% depth of discharge (typical for 17 Ah AGM).

Typical uses: UPS units, alarm and video surveillance (CCTV) systems, emergency lighting, telecommunications, off-grid photovoltaic systems, light electric vehicles (scooters, electric bicycles).

Body dimensions: 181 × 76–77 × 167 mm (L × W × H).
Total height (with terminals): 167 mm (terminals on the top face, level with the case).

Terminals: M5 screw (M5 threaded holes in the top).

Charging and performance parameters

Standby/float charging: 13.60–13.80 V at 20–25 °C.
Cyclic charging: 14.50–14.90 V (some data sheets indicate 14.4–15.0 V).
Maximum recommended charging current: 4.25–5.1 A (maximum)
Typical charging current: 1.7 A
Maximum discharge current: up to 255 A for 5 seconds (peak, not continuous) – typical value for 17 Ah AGM.
Internal resistance: ~16 mOhm (charged battery) – typical value for 17 Ah AGM.

Influence of temperature on capacity

  • at 40 °C: ~102%
  • at 25 °C: 100%
  • at 0 °C: ~85%
  • at -15 °C: ~65%

Self-discharge (at 20–25 °C)

  • after 3 months: ~91% capacity remaining
  • after 6 months: ~82%
  • after 12 months: ~64%