POŻ), alarm systems, emergency lighting and moderate cyclic applications. Main technical features Technology: VRLA (Valve Regulated Lead Acid), AGM – sealed, maintenance-free, can be mounted in various positions.
The 12V40MWS battery (usually denoted MWS 40-12) is a sealed VRLA/AGM battery from MW Power, with a nominal voltage of 12 V and a capacity of 40 Ah (C20), from the economy MWS series, intended in particular for UPS units, fire alarm control panels (P.POŻ), alarm systems, emergency lighting and moderate cyclic applications.
Main technical characteristics
Technology: VRLA (Valve Regulated Lead Acid), AGM – sealed, maintenance-free, can be mounted in various positions.
Nominal voltage: 12 V.
Nominal capacity (C20, 25 °C, 10.5 V cut-off):
Design service life: 3–5 years in buffer (standby) operation, at 20–25 °C, according to EUROBAT for the MWS series (economy line).
Cycle life: up to ~500 cycles at ~50% depth of discharge (typical for 40 Ah AGM).
Typical uses: UPS units, fire alarm control panels (P.POŻ), alarm systems and DSO, emergency lighting, telecommunications, off-grid photovoltaic systems, light electric vehicles.
Dimensions, weight and terminals
Body dimensions: 197 × 165–166 × 170–171 mm (L × W × H).
Total height (with terminals): 170–171 mm (terminals on the top face, level with the case).
Terminals: M6 screw (M6 threaded holes in the top).
Charging and performance parameters
Buffer (standby/float) charging: 13.50–13.80 V at 20–25 °C.
Cyclic charging: 14.40–15.00 V.
Maximum recommended charging current: 12.0–13.0 A (maximum)
Typical charging current: 4.0 A
Maximum discharge current: up to 410 A for 5 seconds (peak, not continuous) – typical value for 40 Ah AGM.
Internal resistance: ~7.8 mOhm (charged battery) – typical value for 40 Ah AGM.
Influence of temperature on capacity
Self-discharge (at 20–25 °C)
No imported reviews for this product.